water cooled industrial chiller
Features of HTI series (standard industrial chillers):
Parameter table
Model | HTIE-40WD | HTIE-50WD | HTIE-60WD | ||
nominal cooling capacity | kw | 124 | 156 | 186 | |
ton | 35.17 | 44.41 | 52.89 | ||
Max power consumption | kw | 41.31 | 52.7 | 59.3 | |
power source | 3PH 380V—415V 50HZ | ||||
refrigerant | type | R22 | |||
control | Thermostatic expansion valve | ||||
compressor | type | Hermetic rotary | |||
power | kw | 18.78*2 | 23.6*2 | 26.9*2 | |
condenser | type | finned copper tube + low noise outer rotor fan | |||
Cooling water flow | m3/h | 26.7 | 33 | 40.9 | |
Tank volume | L | 580 | 620 | 620 | |
evaporator | type | Copper coil built-in storage tank | |||
coolant flow | m3/h | 20.6 | 25.5 | 31.6 | |
Tank volume | liter | 580 | 620 | 620 | |
inlet and outlet | inch | 3 | 3 | 4 | |
pump | Power | kw | 3.75 | 5.5 | 5.5 |
max head | m | 22 | 22 | 22 | |
max flow | m3/h | 5.4 | 5.4 | 5.4 | |
dimension | length | mm | 2000 | 2000 | 2250 |
width | mm | 980 | 980 | 1120 | |
height | mm | 1860 | 1860 | 2100 | |
weight | kg | 870 | 980 | 1120 |
Remarks:
the nominal cooling capacities are based on the following conditions:
a. coolant supply 7C, return 12C, temperature difference 3C to 8C;
b. cooling water inlet 25C, outlet 30C, temperature difference 3.5C to 10C;
If you have any special requirements, please keep us noted.
Specifications, appearances and dimensions are subject to change without notice.