Air Cooled Water Industrial Chiller 8kw To 16kw


air cooled water Industrial chiller---8kw to 16kw
  • Categories:Air Cooled Industrial Chiller (HTIE-A)
  • Brand:HERO-TECH
  • Model:HTIE-3A, HTIE-4A, HTIE-5A, HTIE-6A
  • Type:Air-Cooled
  • Certification:Other
  • Cooling Capability(kw):8kw to 17kw
  • Update Time:03/05/2013
Detailed Info

Features of HTIE series (economicalindustrial chillers):
·    R22 refrigerant, 
·    DANFOSS world famous Hermetic  scroll compressor, 
·    Cast iron pump,
·    Stainless steel built-in tank, 
·    Door mounted disconnect switch,
·    Original Schneider electrical  components, 
·    Standard operating and safety  controls 
·    Ventilated control cabinet 
·    Mounted Casters 
·    Indoor operation 
·    Water-proof electrical chamber
·    Removable panels for easy service  access 
·    Tank level alarm/switch
·    high COP: up to 3.4
Options 
·    System pump pressure bypass  valve 
·    SS pump 
·    Copeland, Sanyo, Daikin compressor 
·    Other type refrigerant, R47c,R134a, R510a,  R404A, etc. 
·    Mounted Casters for bigger  models 
·    Plate heat exchanger/Stainless  steel shell and tube evaporator 
·    Dust filter for condenser 
·    Vibration isolation floor  mounts 
·    Variable speed system pump 
·    Flow switch  
·    Remote operating/monitoring  panel 
·    Hot gas by-pass 

Specification----Air cooled industrial chiller---Packaged and Economical design 

 Model  HTIE-3A  HTIE-4A  HTIE-5A  HTIE-6A
 nominal cooling capacity  kcal/h  6803  10449  11920  13091
 kw 7.91  12.15  13.86  16.22
 Max power consumption  kw  3.37  4.17  5.68  6.38
 power source    3PH  380V-415V  50HZ
 refrigerant  type    R22
 control    Thermostatic expansion valve
 compressor  type    hermetic scroll
 power  kw  2.7  3.5  4.55  5.25
 condenser  type    finned copper tube + low noise outer rotor fan
 evaporator  type    Copper coil built-in storage tank
 coolant flow  m3/h  1.36  2.09  2.22  2.6
 Tank volume  liter  50  60  60  110
 inlet and outlet  inch  1  1  1  1
 dimension  length  mm  980  980  1120  1120
 width  mm  560  560  610  610
 height  mm  1320  1320  1390  1390
 weight  kg  132  145  165  183
Remarks:
1.the nominal cooling capacities are based on the following conditions:
coolant supply 7C, return 12C, temperature difference 3C to 8C;
cooling air inlet 30C, outlet 38C;
2. chiller should be used under 40C.
3. Specifications, appearances and dimensions are subject to change without notice.