Air Cooled Industrial Water Chiller 27kw To 52kw


air cooled Industrial water chiller---27kw to 52kw
  • Categories:Air Cooled Industrial Chiller (HTIE-A)
  • Brand:HERO-TECH
  • Model:HTIE-10AD, HTIE-12AD, HTIE-15AD, HTIE-20AD
  • Type:Air-Cooled
  • Certification:Other
  • Cooling Capability(kw):27kw to 52kw
  • Update Time:03/05/2013
Detailed Info
Features of HTIE series (economical industrial chillers): 

·    R22 refrigerant, 
·    DANFOSS world famous Hermetic scroll compressor, 
·    Cast iron pump,
·    Stainless steel tank built-in, 
·    Door mounted disconnect switch,
·    Original Schneider electrical components, 
·    Standard operating and safety controls 
·    Ventilated control cabinet 
·    Mounted Casters 
·    Indoor operation 
·    Water-proof electrical chamber
·    Removable panels for easy service access 
·    Tank level alarm/switch
·    high COP:2.86 to 3.1 


Options 

·    System pump pressure bypass valve 
·    SS pump 
·    Copeland/Danfoss compressor 
·    Other type refrigerant, R47c,R134a, R510a,R404A, etc. 
·    Plate heat exchanger/Stainless steel shell and tube evaporator 
·    Dust filter for condenser 
·    Vibration isolation floor mounts 
·    Variable speed system pump 
·    Remote operating/monitoring panel 
·    Hot gas by-pass 

Specification -----Air cooled industrial chiller---Packaged and economical design     
 
 Model  HTIE-10AD  HTIE-12AD  HTIE-15AD  HTIE-20AD
 nominal cooling capacity  kcal/h  23840  31046  53406  44548
 kw  27.72  30.8  41.8  51.8
 Max power consumption  kw  11.5  12.9  17.45  21.73
 power source    3PH  380V-415V  50HZ
 refrigerant   type    R22
 control  

Thermostatic expansion valve

 compressor  type    hermetic scroll
 power  kw  4.55*2  5.25*2  7*2  8.96*2
 condenser  type    finned copper tube + low noise outer rotor fan
 evaporator  type    Copper coil built-in storage tank
 coolant flow  m3/h  4.44  5.03  7.1  8.84
 Tank volume  liter  200  200  270  350
 inlet and outlet  inch  2  2  2  2-1/2
 dimension  length  mm  1500  1500  1780  1950
 width  mm  760  760  850  950
 height  mm  1660  1660  1800  1960
 weight  kg  345  382  580  650

Remarks:
1.the nominal cooling capacities are based on the following conditions:
coolant supply 7C, return 12C, temperature difference 3C to 8C;
cooling air inlet 30C, outlet 38C;
2. chiller should be used under 40C.
3. Specifications, appearances and dimensions are subject to change without notice.