Air Cooled Chiller 60kw To 134kw


Air cooled chiller 60kw to 134kw
  • Categories:Air Cooled Industrial Chiller (HTIE-A)
  • Brand:HERO-TECH
  • Model:HTIE-25AD,HTIE-30AD,HTIE-
  • 40AD,HTIE-50AD
  • Type:Air-Cooled
  • Certification:Other
  • Cooling Capability(kw):60KW to 140KW
  • Update Time:02/19/2013
Detailed Info
Features of HTIE series (economical industrial chillers): 
·    R22 refrigerant, 
·    DANFOSS world famous Hermetic scroll compressor, 
·    Cast iron pump,
·    Stainless steel built-in tank, 
·    Door mounted disconnect switch,
·    Original Schneider electrical components, 
·    Standard operating and safety controls 
·    Ventilated control cabinet 
·    Mounted Casters (3HP to 12HP) 
·    Indoor operation 
·    Water-proof electrical chamber
·    Removable panels for easy service access 
·    Tank level alarm/switch
·    high COP: up to 3.1

Options 
·    System pump pressure bypass valve 
·    SS pump 
·    Copeland/Danfoss compressor 
·    Other type refrigerant, R47c,R134a, R510a, R404A, etc. 
·    Mounted Casters for bigger models (above 15HP) 
·    Plate heat exchanger/Stainless steel shell and tube evaporator 
·    Dust filter for condenser 
·    Vibration isolation floor mounts 
·    Variable speed system pump 
·    Flow switch (per module or system) 
·    Remote operating/monitoring panel 
·    Hot gas by-pass 

Specification---Packaged air cooled Industrial chiller
 Model  HTIE-25AD  HTIE-30AD  HTIE-40AD  HTIE-50AD
 nominal cooling capacity  kw 62.1 83.6 106.34 138.2
 power source    3PH  380V-415V  50HZ
 refrigerant  type    R22
 control    Thermostatic expansion valve
 compressor  type    hermetic scroll
 power  kw  10.8*2  13.62*2  18.78*2  23.6*2
 condenser  type    finned copper tube + low noise outer rotor fan
 evaporator  type    Copper coil built-in storage tank
 coolant flow  m3/h  10.06  13.6  17.75  21.9
 Tank volume  liter  350  420  580  580
 inlet and outlet  inch  2-1/2  2-1/2  3  3
 dimension  length  mm  2150  2150  2650  2200
 width  mm  1050  1050  1200  1780
 height  mm  2100  2100  2200  2200
 weight  kg  810  890  1112  1320

Remarks:
1.the nominal cooling capacities are based on the following conditions:
coolant supply 7C, return 12C, temperature difference 3C to 8C;condensing temperature 50C;
cooling air inlet 30C, outlet 38C;
2. chiller should be used under 40C.
3. Specifications, appearances and dimensions are subject to change without notice.